|
| |
R o o f V e n t i l a t i o n
Page 5 of 5
|
|
|
|
|
When determining ventilation, remember the following:
- Intake and exhaust ventilation should be installed at an approximate one to one (1:1)
ratio. More at the eaves is better if it can be attained.
- The 1/300 rule - 1 square foot of attic ventilation (Net Free Vent Area) per 300 square
feet of attic floor space.
- No attic vents should be installed between the intake and exhaust vents.
- There should be at least three feet (3') of vertical distance between
the intake vnets and the exhaust vents.
SOME NOTES:
- FHA Guidelines recommend the 1/300 rule. Some building codes require
the 1/150 rule. When using the example above, adjust your numbers accordingly.
- The Home Ventilating Institute (HVI) recommmends a 60/40 ratio where
60% of the total ventilation is for intake and the remaining 40% is for exhaust.
- Some material manufacturers will not honor their warranty unless
attic ventilation has been installed.
The information found on this page is for
informational purposes. For specific ventilation requirements in your area, consult your
local building code authority.
|
|
<--Previous
|
|
| |
|